Galaxy 2000LD
UPS
UPS, 2000VA, 240W, 7ahx4, 230/50, With 2 Schuko outlets, RJ45 x2, USB
BASIC INFORMATION |
|
| Type | Online UPS |
| Part Number (P/N) | POS2178 |
| EAN | 5600865271734 |
| Model | Galaxy 2000LD |
| Color | Black |
| Outlet type | Shuko |
| Outlets | 2 outlets with power source |
| Implementation | Computers, screens and POS |
| Capacity | 2000VA:1600W |
TECHNICAL SPECIFICATIONS |
|
FUNCTIONS |
|
| Main | Common Neutral design, Double Conversion Topology (O/P Neutral to I/P Neutral is 0 volt normally) Wide Range Input Window and Input Power Factor correction 0.8~0.9 Output Power Factor Low Noise Smart Cooling Fan Design High Efficiency, New Full-bridge Inverter Design Smart backup time estimation (LCD display model) Adjustable floating charging voltage Automatic restart of loads after UPS shutdown Generator compatible Smart battery management |
| Outlets | 2 Schuko outlets with power |
| Display | YES - Time Remaining, consumption and voltage |
INPUT |
|
| Nominal Voltage | 200V/220V/230V/240V Selectable |
| Voltage Range | 100~285V |
| Frequency Range | Under Frequency Converter Mode, 40-70Hz |
OUTPUT |
|
| Capacity | 2000VA:1600W |
| Output Voltage | 200V/220V/230V/240V Selectable |
| Voltage Waveform | Sine Wave |
| Crest Factor | 3:1 |
| Regulation | ±2% of selected output voltage (adjustable by software) |
| Transfer Time | AC to DC: Zero Inverter to bypass: 4ms Typical |
| Overload Protection | > 100% overload alarm 100%~115% for 60 seconds, then transfer to bypass mode; 115%~135% for 10 seconds, then transfer to by pass mode; >135% for 2 seconds, then transfer to bypass mode; If bypass mode is not available, then UPS will shutdown the O/P power |
| AC Mode Efficiency | Up to 92% |
BATTERY |
|
| Type | Maintenance–free sealed, valve-regulated, Lead-Acid 12V, 7Ah or 12V, 9Ah (option) |
| Charging Method | CC+CV with trickle charging, voltage 13.2~13.9 adjustable |
| Recharge Time | 7 hours to 90% |
| Protection |
Over current protection. |
|
Monitoring |
Smart monitoring for failed battery or battery open circuit detection and warning |
OTHERS |
|
| Dimensões (WxHxD) | 450x200x180mm |
| Peso | 19Kg |
| Temperature | Operação: 0ºC~40ºC | Armazenamento: -15ºC~55ºC |
| Humidade | 5 - 95% non condensing |
| Audible Noise | < 45dB |
| Certification | CE |